Use Ensures a better continuity of service
to unattended electrical installations. Limits the number and the cost of on-site
interventions.
Applications Telecommunication and broadcasting. Pumping and water treatment. Street lighting and road signs. Agriculture.
Banks, computing.
Technical
features
Dimensions
H 90 mm x L 105 mm x P 58 mm
Weight
170 g
330 g
Installation
Mounting on DIN rail
Connection
Terminal blocks for 2.5 mm˛ cables
Use
With Schneider 100 to 630 A MCCB's used with residual
current relay
Power supply
230 VAC
48 VDC / 24 VDC
Waking state consumption
30mA
Indicator lamps
Green : in use - flashing red : fault
Internal protection
2,5 kA varistor + 6,3 A fuse
Duration of switch on
# 2 s
Alarm report output
3 points auxilary contact 250 VAC - 5A single
stable
Impulse counter (optional)
LCD 6 digits with reset (retention > 10 years)
Time delay (optional )
Adjustable from 12 s to 8 h
Adjustable from 6 s to 10 h
Operating temperature
- 25° C to + 50° C
Working safety
Switch off when people are on site
Protection index
IP 21
Operating
characteristics of the RNS
In case of tripping due to a sharp fault (short-circuit or earth fault)
only one test is made. In other cases (overcurrent, overvoltage,
temporary fault) three tests are made before the equipment becomes
faulty. This cycle restarts after 5 minutes
without tripping.