Use Ensures a better continuity of service to unattended electrical installations.
Limits the number and the cost of on site interventions.
Applications Telecommunication and broadcasting. Water treatment. Street lighting. Banks, computing.
Technical features
Dimensions
H810 x W890 x D930
Weight
650 g
Installation
Mounting on DIN rail
Use
with Schneider C60 and DT40 MCBs
Power
230 VCA / 48 VCC / 24 VCC / 12 VCC
Sleep mode comsumption
30 mA
Indicator lights
Green: in service - red : fault
Internal protection
Varistor 2,5 kA + fuse 6,3 A
Time for reconnection
# 2 s
Connection
*
Terminal blocks for 2,5mm˛ cables
Remote control input
*
Closing contacts
Remote control impulse
*
> 2s
Alarm report output (fault and Open/close )*
3 points auxilary contact 250 VCA - 6A
Counter
*
LCD 6 digits with reset
Time delay *
Adjustable frome 6 s to 10 h
Oprating temperature
- 25° C to + 50° C
Safety instruction
Switch off when people are on site
Protection index
IP 21
* optional
Operating characteristics In case of tripping due to a sharp fault (short-circuit) only one test is made In other cases (overcurrent, overvoltage, temporary fault) three tests are made before the equipment becomes faulty.
The cycle restarts after 5 minutes without tripping. Possibility of remote control, time delay, counter according to the version.
Part number
For 1-2 poles C60 MCB
For 3-4 poles C60 MCB
230 VAC
48 VCC
12 VCC
230 VAC
48 VCC
12 VCC
Standard
31400
31420
31440
31410
31460
31480
With time delay
(6 s to 10 h)
31401
31421
31441
31411
31461
31481
With time delay and counter
31403
31423
31443
31413
31463
31483
With remote access
31405
31425
31445
31415
31465
31485
With remote access and time delay
31406
31426
31446
31416
31466
31486
With remote access,time delay and counter
31408
31428
31448
31418
31468
31488
Rmodul
/ Automatic recloser for miniature circuit breaker